Two bulbs of 100w and 40w respectively connected in series across a 230v supply which bulb will glow bright and why?

Since two bulbs are in series they will get equal amount of  electrical current but as the supply voltage is constant across the bulb(P=V^2/R).So the resistance of 40W bulb is greater and voltage across 40W is more (V=IR) so 40W bulb will glow brighter.

Why most of analog o/p devices having o/p range 4 to 20 mA and not 0 to 20 mA ?

Answer:4-20 mA is a standard range used to indicate measured values for any process. The reason that 4ma is chosen instead of 0 mA is for fail safe operation .For example- a pressure instrument gives output 4mA to indicate 0 psi, up to 20 mA to indicate 100 psi, or full scale. Due to any problem in instrument (i.e) broken wire, its output reduces to 0 mA. So if range is 0-20 mA then we can differentiate whether it is due to broken wire or due to 0 psi.